>>> 'utilities' problem from bob -- Wed Sep 27 09:10:37 1989 <<<

The air dryer in the basement has been fixed.
The air is up and adjusted to 90 psi.

>>> 'utilities' problem from bob -- Fri Oct  6 07:22:09 1989 <<<

The air dryer in the basement is again not functioning. This is
evidenced by the oil and water now appearing in our air lines.
I walked down to the basement and found the unit off with no
power supplied. This message will be cc'd to Eleta and stateng
(Scott) for service.

>>> 'utilities' problem from bob -- Fri Oct  6 09:56:30 1989 <<<

The air dryer in the basement has been checked by our Stationary
Eng. Scott found power to the unit and therefore there is a problem
within the unit. He has turned in an "A" tag for expedient service.

>>> 'utilities' problem from bob -- Mon Oct  9 14:21:29 1989 <<<

The air dryer was repaired, it had a blown fuse in the control panel.
Reason: Unknown
The dryer has been checked on several occasions and appears to be working
fine.

>>> 'utilities' problem from bob -- Thu Oct 12 16:01:13 1989 <<<

A bridge of the air lines has been run between GL-4 (new lab) and
a tap above the ceiling of the lberg furnaces. Both terminations
have been labeled with their destinations and the old lab is now
being fed from the new lab. The old lab feed is now valved off.

>>> 'utilities' problem from bob -- Wed Oct 18 09:03:32 1989 <<<

The air dryer is again down in the basement. The S.E. has been informed as well
as Eleta and we are awaiting repiars.
Bob

>>> 'utilities' problem from rnorman -- Tue Oct 24 09:28:38 1989 <<<

A Black Max N2 gun was installed between tylan banks 2 & 3 and at bank 1.
These are N2 guns not anti-static guns.  Each gun pressure can be set 
individually, and are now set at 40 PSI.  They are ready for use.

>>> 'utilities' problem from bob -- Tue Oct 24 10:25:40 1989 <<<

The air dryer in the basement has been restored to service.
It is operating correctly.

>>> 'utilities' problem from rnorman -- Fri Oct 27 13:16:47 1989 <<<

The deck hose on the old lab sink has cracked a H2O leak.  The main
water valve to the hose was turned off.

>>> 'utilities' problem from bob -- Mon Oct 30 15:40:18 1989 <<<

There is a steam or water leak coming from an area near the steam valve
in Rm. 546 Cory Hall. It is associated with the Microlab air intake.
It should be reported to P&FM.
This note will be cc'd to Eleta for a call in and to Scott McNally.

>>> 'utilities' problem from jimmoon -- Wed Nov  1 15:03:29 1989 <<<

We're running very low on DI water.  Just a trickle in sinks6-8.

>>> 'utilities' problem from evan -- Thu Nov  2 08:25:07 1989 <<<

Problem with excess di use has been moved to rodi problems.  rodi system
is running at proper levels now and is being monitored today.

>>> 'utilities' problem from bill -- Thu Nov 16 19:49:03 1989 <<<

Phone problem :

the -2796 line is continuously tied up -
I checked all phones in the lab - but none were
off the hook. The office was dark  ( so no one was using it in there )
and locked - so I couldn't check in there.

Probably a quick fix somewhere - just frustrating not being
able to call out

>>> 'utilities' problem from bob -- Wed Nov 22 07:48:39 1989 <<<

A leaking steam valve in Rm 546 has been serviced. It will be monitored
for leaks.

>>> 'utilities' problem from bob -- Fri Jan 12 15:06:35 1990 <<<

A request to OPR (Office of Physical Resources) aka PFM, aka DOFM, 
aka Physical Plant, aka Grounds and Buildings, has been made to
have them service our spare recirc system pump. Jim Wilson of the
plumbing shop is in touch with the Maintenance Machinists. They
will work out who will take charge of this repair.
An update to this report is pending Jim's return phone call.

>>> 'utilities' problem from bob -- Wed Jan 17 15:42:34 1990 <<<

The problem for the recirc pump will be removed from the
e-stat appt mail will be prompted to remind me to place 
a call and check on the status for rebuild in 30 days.

>>> 'utilities' problem from bob -- Fri Jan 19 15:39:30 1990 <<<

# new LOX cylinders were installed this afternoon in the rear of
Cory Hall. These came from our new vendor Airco, the successor
of Amerigas. O2 is up.

>>> 'utilities' problem from bob -- Tue Feb 20 11:52:36 1990 <<<

The old lab air feed from the west side of the building has been
valved back on. This feeds the lab from both the west and the 
east building risers, our normal mode. 
This valve had been closed during the construction on the first
floor. Operations are better with this feed open.

>>> 'utilities' problem from bob -- Tue Feb 27 09:16:57 1990 <<<

The lab suffered a loss of air pressure and also a loss of
N2 back up pressure this am. The likely cause was the loss of
air pressure due to a shutdown of the compressors in the basement
accompanied by the backfeeding of N2 to the rest of the building.

An unscheduled shutdown is the likely cause!

A check valve will be ordered and added to the old lab air
feed. This will prevent backfeeding the building in the
future.

Eleta is looking into who shut off the air.

>>> 'utilities' problem from phillip -- Mon Mar  5 14:20:02 1990 <<<

P: Failed ICW check valve allowing H2o to flow thru
   the lab back into bldg supply.
S: Replaced failed plast-o-matic valve with spring loaded
   brass check valve in the aux. supply line. The ICW
   is back on line.

>>> 'utilities' problem from phillip -- Thu Mar  8 08:36:04 1990 <<<

Check valves have been added to the pneumatic line 
in the oldlab.
This will prevent n2 from back feeding the rest of the
building when the air compressors go down.

>>> 'utilities' problem from phillip -- Thu Mar  8 09:17:56 1990 <<<

P: Microlab supply air is excessive in volume.
   Also, the temperature is low.

 Eleta, please report this to John Tusting/DOFM.
thank you

>>> 'utilities' problem from phillip -- Thu Mar  8 14:17:17 1990 <<<

John T. swapped, to their correct positions, a pilot control line
and a delivery control line (both steam).
 There is remaining a case of trouble on the steam valve itself
that John referred to the steamfitters.

>>> 'utilities' fix from evan -- Fri Apr 27 16:55:00 1990 <<<

As of 17:00 today, recirc loop resistivity has risen to 460Kohm. 

>>> 'utilities' fix from evan -- Tue May  8 09:59:11 1990 <<<

The recirc loop resistivity had dropped to 100K ohms.  A new resin cartridge
was installed.  This is first replacement since this polishing loop added.

>>> 'utilities' fix from bob -- Fri May 11 08:21:58 1990 <<<

There is a report of low oxygen pressure. A check of the LOX in
the backyard reveals a full cylinder; however, it was not valved
on. It has been turned on and the pressure restored. 

There are currently two empties which need re-ordering. This note
will be cc'd to Susan Kellogg for re-order.